Instructions for Heater for Large Volume Press

Major changes since last revision: Flukes replaced with Keithley Digital MultiMeter; previous revision says nothing about Epics.

Heating the sample for LVP runs involves sending a controlled current through a furnace and reading the temperature with a thermocouple. This involves controlling and monitoring the heater power supply voltage and current, as well as the temperature. The MEDM screens which enable these controls are shown below.

First, we have the main screen:

The two relevant buttons on this screen are Heater and Keithley and Other electronics:

Heater Keithley and Other electronics

Most of the signals are processed by the Keithley Digital Multimeter, and we will look at that later. The buttons on the Heater menu point to various functions for monitoring and controlling the temperature:

Monitor Temp, Pressure & LVDTs

Using the middle mouse button in any of the data boxes, you can identify the Process Variable (PV) associated with that reading. For the above screen, these are:

Name on window
PV
Units
Heater Power X17B2:LVP_furnace_calcs.D Watts

Temperature (Tc1)

X17B2:LVP_tc1_calcs.I °C
Temperature (Tc2) X17B2:LVP_tc2_calcs.I °C
LVDT: Gap X17B2:scaler1_calc2.VAL mm
LVDT: Bottom X17B2:scaler1_calc3.VAL mm
Oil Pressure (bars) X17B2:LVP_furnace_calcs.G bars
Load (Tons) X17B2:LVP_furnace_calcs.H tons
Pump Speed X17B2:DMM1Ch7_calc.VAL % of Max
Pump Position X17B2:DMM1Ch8_calc.VAL % of Max

All these lines point to specific lines on other windows, shown below.

We will be concerned with the first three lines only for the discussion of the heater. These all refer to calculations made in a userTransform. The thermocouple calculations are performed in the Thermocouple #1 Calculations and the Thermocouple #2 Calculations windows.

Thermocouple #1 Calculations

If you look at line I in this transform, you see the equation B+A*C+A^2*D+A^3*E+A*4*F+A^5*G*A^6*G. The letters A, B, C, D, E, F, G, and H refer to the values in the 4th column of the corresponding row. A is the reading of the thermocouple from the Keithley, in milliVolts. The calibration coefficients, B, C, D, E, F, G, and H, listed in the second column can either be typed in manually, or loaded using an IDL program called load_thermocouple_cal.pro, listed below:

pro load_thermocouple_cal, index, meter

if (n_elements(index) eq 0) then message, 'Usage: load_thermocouple_cal, tc_index, meter'
if (n_elements(meter) eq 0) then message, 'Usage: load_thermocouple_cal, tc_index, meter'
if (index lt 1) or (index gt 10) then message, 'tc_index must be between 1 and 10'
if (meter lt 1) or (meter gt 2) then message, 'meter must be between 1 and 2'

; This file loads the thermocouple calibration
; Thermocouple conversion coefficients (10)
coeffs = [ $
0,1,0,0,0,0,0, $
25.35814157,72.21224989,-2.815357654,.1698181988,-.46996988e-2,.5418247356e-4,-.2645913896e-7, $
28.842,23.987,0,0,0,0,0, $
30.41082384,71.48460400,-2.653841116,0.1534199600,-0.3953438497E-02,0.4242474276E-04,-.1766276156E-07, $
30.09713989,72.75952978,-3.348950307,0.2665505800,-0.1173597651E-01,0.2818261953E-03,-.2733066876E-05, $
25.05262657,69.37059567,-2.017625153,0.0891823577,-8.1251251339e-04,-.3226719000e-04,0.6820774988e-06, $
25.30200973,70.55820145,-2.387582938,0.1299370657,-0.2870959470E-02,0.1619613496E-04,0.2519157716E-06, $
28.37065525,74.04641335,-1.452700146,-.04483512603,0.7197806231E-02,-.2381368548E-03,0.2612083841E-05, $
19.41832589,75.29103822,-2.118950549,0.04461300802,0.1919626434E-02,-.9391041392E-04,0.1124852894E-05, $
20.61286273,75.229305278,-1.99131594,0.02906734054,0.2671442980E-02,-1.105697512E-04,0.1264764189E-05]

coeffs = reform(coeffs, 7, 10)
desc = ['Volts', 'W-Re type C', 'Type K', 'W-Re type C', 'W-Re type C', 'W-Re type C', 'W-Re type D', $
'W-Re type D', 'W-Re type D', 'W-Re type D']
prefix = 'X17B2:Fluke'+strtrim(meter,2)+'_Calc'
letters = ['B', 'C', 'D', 'E', 'F', 'G', 'H']
t = caput(prefix+'.DESC', desc[index-1])
for i=0, 6 do begin
t = caput(prefix+'.INP'+letters[i], string(coeffs[i,index-1], format='(e20.12)'))
endfor
end

Line A in the transform screen tells you that the thermocouple reading comes from Keithley#1 channel 1 (DMM1Ch1).

Let's look at the Keithley screen now:

If you press the More button, you get another menu from which you can select either the 1st 10 channels, or channels 11 through 22 (we don't use the Genersl SCPI Input button).

 

Keithley main screen
...more

Pressing Multi-channel 1-10, you get:

Multi-channel 1-10

If you were to point to the PV for channel 1 labeled RAW:, you would get: X17B2:DMM1Ch1_raw.VAL, while if you were to point to the PV for channel 1 labeled CALC:, you would get: X17B2:DMM1Ch1_calc.VAL There is a calculation built into this window to convert Volts to milliVolts, which is why we use DMM1Ch1_calc rather than DMM1Ch1_raw.

The heater can be controlled bi either the Heater Power Supply window (labeled Power Supply #1 10V 250A in the Heater menu) or the Furnace Control window (labeled LVP furnace #1 in the same menu). I will discuss them both here.

Heater Power Supply #1

Name on window
PV
meaning
Volts X17B2:DMM1Ch5_calc.VAL measured voltage across heater
Value (numeric) X17B2:DAC1_1.VAL  
  X17B2:DAC1_1_tweak.A button to lower voltage by tweak value
Value (graphic) X17B2:DAC1_1.VAL  
  X17B2:DAC1_1_tweak.B button to raise voltage by tweak value
Tweak X17B2:DAC1_1_tweakVal amount of tweak
unlabeled bar graph for volts X17B2:DMM1Ch5_calc.VAL  
Amperes X17B2:DMM1Ch6_calc.VAL measured heater current using current sensor
Value (numeric) X17B2:DAC1_3.VAL  
  X17B2:DAC1_3_tweak.A button to lower current by tweak value
Value (graphic) X17B2:DAC1_3.VAL  
  X17B2:DAC1_3_tweak.B button to raise current by tweak value
Tweak X17B2:DAC1_3_tweakVal amount of tweak
unlabeled bar graph for volts X17B2:DMM1Ch6_calc.VAL  
Temperature (Tc1) X17B2:LVP_tc1_calcs.I temperature from Tc1 using calculation record above
Temperature (Tc2) X17B2:LVP_tc2_calcs.I temperature from Tc2 using calculation record above
EMF (Tc1) X17B2:DMM1Ch1_calc.VAL reading in mV of Tc1 using Keithley
EMF (Tc2) X17B2:DMM1Ch2_calc.VAL reading in mV of Tc1 using Keithley

Furnace Control for Power Supply #1

Name on window PV meaning
Current limit X17B2:LVP_AMP_tweak_down.PROC  
  X17B2:DAC1_3  
  X17B2:LVP_AMP_tweak_up.PROC  
Current control tweak X17B2:LVP_AMP_tweak  
Voltage Limit X17B2:LVP_VOLT_tweak_down.PROC  
  X17B2:DAC1_1  
  X17B2:LVP_VOLT_tweak_up.PROC  
Voltage limit tweak X17B2:LVP_VOLT_tweak  
Temperature X17B2:LVP_furnace_calcs.E  
Temperature setpoint X17B2:SP_tweak_down.PROC  
  X17B2:SP_tweak_down.PROC  
  X17B2:SP_tweak_up.PROC  
Temperature setpoint tweak X17B2:LVP_SP_tweak  
Heater Voltage (actual) X17B2:LVP_furnace_calcs.A  
Heater current (actual) X17B2:LVP_furnace_calcs.B  
Heater power X17B2:LVP_furnace_calcs.D  
Heater resistance X17B2:LVP_furnace_calcs.C  
Control Mode X17B2:VoltageMode  
unlabeled X17B2:LVP_mode_reset.PROC  
Quench X17B2:LVP_quench.PROC  
Feedback X17B2:LVP:PID1.FBON  

At the bottom of the screen there is a More button:

Furnace calcs

The heater voltage and current are indicated in four different places (each); each place has a different meaning. Three of these places can be seen by pressing the Monitor PS1 button at the bottom of the Keithley and Other Electronics menu:

It is the yellow readings with which we are concerned.

The first yellow row (Actual Volts & Amps) is the reading directly off the press. The volts reading comes from the wires connect to the top and bottom halves of the press which go directly to the Keithley channel 5. The current reading comes from the current sensor which feeds the Keithley channel 6 (after a conversion).

The second row (Control Volts calculated) represents the desired voltage fed into the the DACs, and represents the voltage and current desired. Due to losses in the system, they will be slightly different from the Actual Volts & Amps line.

The third row (Control Volts read) represents the same control voltages from the DACs). Again, they should be the same as the Control Volts calculated, within error. If they are substantially different, then either the DACs are faulty, or there is a bad connection.

Finally, the power supply itself has readouts, which can only be seen using the video camera. Its values will be greater than the Actual readings, because of resistance in the heater leads, and inaccuracies in the meters.